Required Number of Lighting Circuits – Nondwelling
- Posted by Paul Abernathy
- Categories Blog
- Date March 17, 2023
- Comments 0 comment
Required Number of Lighting Circuits - Nondwelling
Required Number of Lighting Circuits
The required number of lighting circuits is calculated for the connected load. The connected load is the load in volt-amps before any demand factors are applied. The connected load is the area inside a building in square feet multiplied by the required volt amps per square foot.
Table 220.42(A) provides the volt amps per square foot. This load is already sized at 125%. To determine the required current for the lighting load, divide the connected load by the voltage of the lighting load.
The voltage for the lighting load is usually 120 V or 277 V, but it may also be 208 V, 240 V, or 480 V. To determine the number of circuits, divide the load by the size of the circuit breaker (CB). CB sizes for general lighting loads are typically 15 A or 20 A. If the answer is not a whole number, round up to the next whole number.
For example, how many circuit breakers are required for the lighting circuits in a 50,000 sq ft manufacturing facility? The voltage for the manufacturing facility is 120/240 V, and 20 A CBs are used.
Step 1: Number of circuit breakers = 2.2 VA/sq ft x area of building / voltage
Step 2: Sum of Step 1 / circuit breaker rating
In the example : 2.2 VA x 50,000 = 110,000 VA / 120V = 916.66 / 20 = 45.83 – Round up to 46
Solution: Number of circuit breakers = 46
Note: The 2.2 VA per sq. ft comes from Table 220.42(A) in the 2023 National Electrical Code, it is 220.12 in earlier editions.
CEO and Founder of Electrical Code Academy, Inc. A Virginia Corporation located in Mineral, Virginia
You may also like
Grounding vs Bonding in the 2026 NEC: Equipment Grounding Conductors, Bonding Jumpers, and Article 250 Explained
⚡ 2026 NEC • Article 250 Technical Review Grounding Conductors vs. Bonding Conductors in the 2026 NEC:Stop Calling Everything a “Ground” One of the biggest reasons Article 250 still creates confusion in the field is because people use the word …
2026 NEC • Article 392 • Student Lesson Can Single Insulated Conductors Like THHN Be Installed in Cable Trays? Article 392.10 is one of those NEC sections that sounds simple until you slow down and separate two very different questions: …
Selective Coordination in Article 700: Stop Forcing a 0.1-Second Rule That Doesn’t Exist
⚡ Selective Coordination in NEC 700: The 0.1-Second Myth Needs to Go Selective coordination is one of those topics that sounds simple until people start blending rules from different occupancies and different Code sections. That is where the confusion starts. …