Sizing Wireways – Both Nonmetallic and Metallic
- Posted by Paul Abernathy
- Categories Blog
- Date March 17, 2023
- Comments 0 comment
Sizing Wireways Made Easy
Sizing Wireways
Sizing a wireway to hold a predetermined number of conductors is similar to sizing raceways.
First, determine the total area of the conductors in square inches. This is found by using Table 5 for insulated conductors, Table 5A for compact conductors, or Table 8 for bare conductors. Take the total area of these conductors, divide by 20% or multiply by 5, and take the square root to find the appropriate size wireway.
For example, what size of wireway is required for the following THNN conductors?
- Four 600 kcmil THNN conductors
- Four 400 kcmil THNN conductors
- Three 300 kcmil THNN conductors
See Table 5 to determine the area of each conductor.
600 kcmil THHN = 0.8676 sq in.
400 kcmil THHN = 0.5863 sq in.
300 kcmil THHN = 0.4608 sq in.
Next, Multiply the area by the number of conductors:
0.8676 sq in. × 4 = 3.4704 sq in.
0.5863 sq in. × 4 = 2.3452 sq in.
0.4608 sq in. x 3 = 1.3824 sq in.
Add the area of all the conductors: 3.4704 + 2.3452 + 1.3824 = 7.198 sq in.
Now, take the total area (7.198 sq. in) and divide it by 5, and take the square root it:
7.198 x 5 = 35.99 square root is: 5.99”
The next highest standard wireway size from 5.99” is 6” x 6”
Let’s Confirm: 6” x 6” is 36 Inches x 20% = 7.2 sq in. and as you saw above our conductors took up 7.198 sq. in. so the 6” x 6” wireway is perfect.
Do you need to learn the National Electrical Code? Well, there is no better program than our Fast Trax Programs. If you are preparing for an electrical exam then check out this video on the Fast Trax Black Program.
Sizing Neutrals (Grounded) in a Parallel Service Explained
Understanding Noncoincident Loads for Multifamily Dwellings
Motors | Single Motor Branch Circuit Conductors
Metal-Clad Cable with Nonmetallic Boxes?
Electrical Exam Preparation
Prepare for Your Master or Journeyman Electrician Exam
CEO and Founder of Electrical Code Academy, Inc. A Virginia Corporation located in Mineral, Virginia
You may also like
Electrical Code Academy Announces Launch of Certified Thermal Electrician™ Program
Program Launch Announcement Certified Thermal Electrician™ Program: Thermography Built Only for Electricians A first-of-its-kind thermal imaging certification created specifically for electricians and electrical contractors. Mineral, Virginia – November 14, 2025 Electrical Code Academy, Inc. has announced the launch of the …
Certified Thermal Electrician™ Program — Standards Equivalency & Alignment Statement
Certified Thermal Electrician™ — Standards Equivalency & Alignment Statement Certified Thermal Electrician™Standards Equivalency & Alignment Statement Issued by: Electrical Code Academy, Inc. Program Owner: Certified Thermal Electrician™ Founder & Instructor: Paul Abernathy, CMECP®, Master Electrician, NEC® Code Expert, NFPA CMP-5 …
Why Thermal Imaging Absolutely Matters in Residential Electrical Systems Debunking the Myth: “You can’t find anything in a lightly loaded home.” Some homeowners—and even a few electricians—assume infrared inspections are pointless in houses because most circuits aren’t running anywhere near …