Question:
An apprentice installs a subpanel in a detached garage. The neutral and ground bars are bonded together in the subpanel. What is the issue?

[Bonus]: What additional conductor is required in this setup?

Drop your answer AND NEC reference if you know it ⚡

Please Comment & Discuss Below.

Disclaimer: As always with my questions, there may be errors or mistakes: feel free to call them out!

⚡ I hope you all have a great FRIDAY! and an AWESOME weekend! We are always learning here!

⚡ Credit: TRADEHOG.NET ⚡

Jonathan Battles

250.6

Joshua Audette


SPOILER: ANSWER KEY BELOW


2023 NEC (NFPA LINK)


250.32 Buildings or Structures Supplied by a Feeder(s) or Branch Circuit(s).

(B) Grounded Systems.
(1) Supplied by Feeders or Branch Circuits.

250.6 Objectionable Current.

(A) Arrangement to Prevent Objectionable Current. [as noted by Jonathan]

The Correct answer would be (C). It creates Parallel neutral current paths (the neutral and ground are improperly bonded in the subpanel, creating a parallel neutral current path that allows objectionable current to flow on the equipment grounding conductors and metal parts).