⚡ Question Of The Week ⚡

Question:
For a 120V residential branch circuit installed in Schedule 40 PVC conduit under a driveway, what is the minimum burial depth required according to the NEC?

Drop your answer AND NEC reference if you know it ⚡

💬 Comment & discuss below.

⚠️ Disclaimer: Question may be simplified or test interpretation — verify all answers with NEC text.

⚡ Hope everyone had a great week, and happy Friday! Enjoy the weekend and try to learn something!

⚡ Credit: TRADEHOG.NET ⚡

Eric T.

Table 300.5(A) Column 4

Joshua Audette

SPOILER: ANSWER KEY BELOW


2023 NEC (NFPA LINK)


300.5 Underground Installations.
(A) Minimum Cover Requirements.

Table 300.5(A) Minimum Cover Requirements, 0 to 1000 Volts ac, 1500 Volts dc, Nominal, Burial in Millimeters (Inches)

The Correct answer would be (D). 24 inches. (Column 4 as Mentioned by Eric)