⚡Question Of The Week⚡
Question:
A 125-volt, 20-amp receptacle is installed in the ceiling of a dwelling-unit garage to supply a garage door opener. Is GFCI protection required?
Please Comment & Discuss Below.
Note: As always with my questions, there may be errors; feel free to call these out, as it teaches me to create better questions!
Have a great, productive week, everybody! always learning!
Credit: TRADEHOG.NET
Spoiler below.
-
Answer via: TRADEHOG.NET
GFCI protection is required.
Under NEC 210.8(A)(2), in dwelling-unit garages, all 125-volt, single-phase, 15- and 20-amp receptacles must have GFCI protection. The rule is based on the location (garage), not the mounting height or whether it’s on the ceiling for a door opener.