⚡Question Of The Week⚡

Question:

A 125-volt, 20-amp receptacle is installed in the ceiling of a dwelling-unit garage to supply a garage door opener. Is GFCI protection required?

Please Comment & Discuss Below.

Note: As always with my questions, there may be errors; feel free to call these out, as it teaches me to create better questions!

Have a great, productive week, everybody! always learning!

CreditTRADEHOG.NET

Joshua Audette

Spoiler below.

-

Answer via: TRADEHOG.NET

GFCI protection is required.

Under NEC 210.8(A)(2), in dwelling-unit garagesall 125-volt, single-phase, 15- and 20-amp receptacles must have GFCI protection. The rule is based on the location (garage), not the mounting height or whether it’s on the ceiling for a door opener.