Question: A dwelling unit has:

• General lighting: 3,000 VA

• Small appliance circuits: 3 × 1,500 VA

• Laundry: 1,500 VA

• Dryer: 5,000 VA (240V)

• Range: 8,000 VA

What is the MINIMUM service load (VA) before converting to amps?

Drop your answer, math AND NEC 2026 reference if you know it ⚡

💬 Comment & discuss below.

⚠️ Disclaimer: Question may be simplified or test interpretation — verify all answers with NEC text.

⚡ Happy Friday, all! Enjoy this little code calculation exercise!

⚡ Credit: TRADEHOG.NET ⚡

Eric T.

Studying load calcs now. If I've done it right, 5100va for general lighting and receptacles. Table 220.45

Column B of 220.55 Note 4 for one range between 3.5kw to 8.75kw so 80% of 8kw.

Clothes dryer min is 5kw. 220.54

No fastened in place appliances mentioned. No heat or air mentioned.

Paul Abernathy

Eric Taylor Greetings Eric,

Ok, so this post is in the 2026 NEC Forum so it would be 120.55. However, Note 4 is about branch circuit and not the overall service so Note 4 would not be appropriate.

Now, you are on the right track but in the case of the Range, you get to choose between Column B or C and take the lesser which I believe you did. So ..you are tracking ..

Joshua Audette

⚡ SPOILER: ANSWER KEY BELOW ⚡

────────────────────────

2026 NEC

────────────────────────

General Lighting = 3,000 VA

Small Appliance Circuits = 3 × 1,500 VA = 4,500 VA

Laundry = 1,500 VA

Total = 9,000 VA

Per the dwelling-unit demand factors:

First 3,000 VA = 3,000 VA

Remaining 6,000 VA × 35% = 2,100 VA

Demanded Load = 5,100 VA

Dryer = 5,000 VA

Range = 8,000 VA × 80% = 6,400 VA

Total Service Load:

5,100 + 5,000 + 6,400 = 16,500 VA

The Correct Answer would be (A). 16,500 VA. NEC References: Article 120, 120.52(A), 120.52(B), 120.54, and Table 120.55 Column B.