⚡ QUESTION OF THE WEEK (2026)
An electrician is calculating the maximum demand load for a dwelling-unit feeder supplying four household electric ranges.
The ranges have the following nameplate ratings:
- 10 kW
- 14 kW
- 15 kW
- 21 kW
According to the 2026 NEC, what is the maximum demand load for these ranges?
💬 Comment your answer and identify the NEC section(s) you used.
⚡ 2026 NEC
⚡ Study Credit: TRADEHOG.NET
🔥 Also check out new releases on FastTraxTube!
⚠️ Educational question. Verify all requirements using the applicable NEC edition and local amendments.
❗ Answer in the comments — and tell us what NEC section you used!
10++14+15+21=60,
60/4=15, 15-12=3,3x5=15 %(120.55 note 2)
4 ranges col C= 17(120.55 table) 17x1.15=19.55
19.55KW