⚡ Question Of The Week ⚡ (2026 NEC)

#QuestionOfTheWeek2026: Can You Apply the Noncoincident Load Rule?

A feeder supplies the following two motor-operated loads:

30A air compressor

24A dust collector

The equipment is listed and designed so only one load can operate at a time.

According to the 2026 NEC, what is the minimum calculated load for this feeder?

💬 Comment your answer AND explain why below.

⚠️ Disclaimer: Question may be simplified for educational purposes. Verify all requirements using the current NEC and any applicable local amendments.

⚡ Study Credit: TRADEHOG.NET ⚡

Good luck, code nerds. ⚡

⚡ Question Of The Week ⚡ (2026 NEC)

A compressor is a motor load and the branch circuit is to be calculated at 125% per NEC®️ 430.22.

Joshua Audette

David Engelhart CMECP®️ spot on! ⚡💯 Easy to miss the 125%- Thanks David!