Have a good trip. Can we next week talk about the changes to the emergency disconnect in the 2026
230.85 (Emergency Disconnects) as a standalone section is deleted.
The requirements are consolidated into 230.70(A)(1) for one- and two-family dwellings.
That new language says the service disconnecting means must be installed outdoors (on the building or within sight of it, in a readily accessible location).
The marking provisions that were in 230.85 carry over — the service disconnect will still need to be marked as both:
“EMERGENCY DISCONNECT – SERVICE DISCONNECT”
So yes — moving forward under the 2026 NEC:
-
For dwellings, you won’t be able to put the service disconnect inside anymore.
-
The outdoor disconnect also serves as the emergency disconnect and has to be labeled accordingly.