Calculating the ampacity of copper and aluminum busbars has never been easier.
Busbars are used in switchboards, load centers, and panelboards. Busbars are generally uninsulated. The constant amperage for a bare copper wire (Cu) busbar must not exceed 1000 A sq in. of the cross-sectional area of its bar.
Aluminum (Al) busbars may not endure constant amperage exceeding 700 A sq in. of the cross-sectional area of the bar per 366.23 (A). To calculate the ampacity of a busbar, apply the following equation.
Busbar ampacity= T x W x constant, where busbar ampacity = ampacity of busbar (in A)
f = thickness (in in.)
w = width (in in.)
constant 1000 for Cu and 700 for Al
Examples:
What is the ampacity of a ¼” thick by 3″ wide Cu busbar?
Busbar ampacity= T x W x Constant
Busbar ampacity 0.25” x 3” x 1000
Busbar ampacity=0.75 x 1000
Busbar ampacity 750 A
What is the ampacity of a ½” thick by 2” wide Al busbar?
Busbar ampacity=T x W x Constant
Busbar ampacity 0.50” x 2” × 700
Busbar ampacity= 1x 700
Busbar ampacity= 700 A
Heat Never Lies: The New Preventative Maintenance Strategy Data Centers Can’t Afford to Ignore
Concerns Regarding NFPA Link Terms and Conditions for Educational Use
Sizing Neutrals (Grounded) in a Parallel Service Explained
Fast Trax Supreme + StudyHog AI: The Ultimate Electrician Exam Prep System
Dissecting Electrical Exam Prep Questions: Finding the Root of the Question
Major Changes Coming Soon | Electrical Code Academy, Inc.
CEO and Founder of Electrical Code Academy, Inc. A Virginia Corporation located in Mineral, Virginia
You may also like
2026 NEC • Article 392 • Student Lesson Can Single Insulated Conductors Like THHN Be Installed in Cable Trays? Article 392.10 is one of those NEC sections that sounds simple until you slow down and separate two very different questions: …
Selective Coordination in Article 700: Stop Forcing a 0.1-Second Rule That Doesn’t Exist
⚡ Selective Coordination in NEC 700: The 0.1-Second Myth Needs to Go Selective coordination is one of those topics that sounds simple until people start blending rules from different occupancies and different Code sections. That is where the confusion starts. …
2026 NEC 250.122(F) Change: New Rules for Equipment Grounding Conductors in Parallel Raceways
Code Change Analysis 250.122(F) in the 2026 NEC: Smarter EGC Sizing or a Step Away from Proven Protection? One of the most discussed revisions in the 2026 NEC involves parallel raceways and the sizing of the equipment grounding conductor. While …