Installing Conductors in Existing Raceways
- Posted by Paul Abernathy
- Categories Blog
- Date March 17, 2023
- Comments 0 comment
Installing Conductors in Existing Raceways
INSTALLING CONDUCTORS INTO EXISTING RACEWAYS
It is common for electricians to install conductors into a conduit raceway system that already has conductors installed in them. If this is the case, the amount of space being used by the conductors must be determined in order to know the amount of space available to insert more conductors.
Apply the following steps to determine the number of conductors that may be added to a conduit:
- Determine the space occupied by existing conductors by using Table 5,
- Determine the allowable fill (typically 40%) based on conduit type and the number of conductors already installed. See Table 4 for the type of conduit.
- Subtract the total conductor area from the allowable fill to find the remaining space left.
- Divide the remaining space by the area in square inches of the new conductors being installed. The area for conductors is found in Table 5
For Example: What is the remaining available area of a 2” Trade side EMT with (12) 8 AWG THHN Conductors? Use the steps above to solve.
Step 1: (1) single 8 AWG THHN has an approximate area of: 0.0366 in², Multiple 0.0366 x 12 = 0.4392 in²
Step 2: Since we have Over 2 Conductors, we must look at Chapter 9 Table 1, and determine the maximum fill is 40%. Next, we visit Chapter 9, Table 4, and find out what the 40% fill is, which happens to be 1.342 in².
Step 3: Using Step 2, 40% allowable fill of 1.342 in² and subtract the (12) conductors’ approximate area of 0.4392 in² from Step 1. (i.e.) 1.342 in² – 0.4392 in² = 0.9028 in² remaining space left.
To complete Step 4, let’s see how many more 8 AWG THHN Conductors we could add to this EMT raceway.
Step 4: Value from Step 3, which is 0.9028 in² / 0.0366 in² = 24.66, drop the .66 and you could place (24) more 8 AWG THHN Conductors in the Trade Size 2 EMT Raceway.
PRO TIP– Since all the conductors are the same you could have used Informative Annex C to determine the maximum number permitted, which is 36 conductors. To show our example calculation works, take our original (12) 8 AWG THHN Conductors and add the (24) more we added from our example for a total of 12 + 24 = 36.
Note: Just because we can put (36) 8 AWG THHN CU Conductors in a Trade Size 2 EMT raceway doesn’t mean that those conductors will have the ampacity necessary to do the job. If they are current carrying conductors (CCC), then 310.15(C)(1) will limit their current carrying ability.
Sizing Neutrals (Grounded) in a Parallel Service Explained
Understanding Noncoincident Loads for Multifamily Dwellings
Motors | Single Motor Branch Circuit Conductors
Metal-Clad Cable with Nonmetallic Boxes?
Electrical Exam Preparation
Prepare for Your Master or Journeyman Electrician Exam
CEO and Founder of Electrical Code Academy, Inc. A Virginia Corporation located in Mineral, Virginia
You may also like
Grounding vs Bonding in the 2026 NEC: Equipment Grounding Conductors, Bonding Jumpers, and Article 250 Explained
⚡ 2026 NEC • Article 250 Technical Review Grounding Conductors vs. Bonding Conductors in the 2026 NEC:Stop Calling Everything a “Ground” One of the biggest reasons Article 250 still creates confusion in the field is because people use the word …
2026 NEC • Article 392 • Student Lesson Can Single Insulated Conductors Like THHN Be Installed in Cable Trays? Article 392.10 is one of those NEC sections that sounds simple until you slow down and separate two very different questions: …
Selective Coordination in Article 700: Stop Forcing a 0.1-Second Rule That Doesn’t Exist
⚡ Selective Coordination in NEC 700: The 0.1-Second Myth Needs to Go Selective coordination is one of those topics that sounds simple until people start blending rules from different occupancies and different Code sections. That is where the confusion starts. …