Understanding the 10-Foot Secondary Conductor Rule in the 2023 NEC
Understanding the 10-Foot Secondary Conductor Rule in the 2023 NEC: Section 240.21(C)(2)
The 10-foot secondary conductor rule, outlined in 240.21(C)(2) of the 2023 National Electrical Code (NEC), provides an exception to the general requirement for overcurrent protection at the source of transformer secondary conductors. This rule allows certain installations to omit overcurrent protection at the transformer, provided strict conditions are met.
This article explains the rule, provides a corrected example for a three-phase transformer, and clarifies why the connected load may differ from the transformer’s full-rated capacity.
What is the 10-Foot Secondary Conductor Rule?
The NEC permits transformer secondary conductors to extend up to 10 feet without overcurrent protection at the source, provided the following conditions are satisfied:
Conditions for Compliance
- Conductor Length: The secondary conductors must not exceed 10 feet in length.
- Ampacity: The ampacity of the secondary conductors must be at least:
- Equal to the calculated load served by the conductors, or
- Equal to the rating of the overcurrent protective device (OCPD) that terminates the secondary conductors, whichever is greater.
For field installations, the ampacity of the secondary conductors must also meet the following formula:
Ampacity ≥ (Primary OCPD Rating ÷ Primary-to-Secondary Voltage Ratio) × 0.1
- Overcurrent Protection: Overcurrent protection must be installed at the termination of the secondary conductors.
- Physical Protection: The secondary conductors must be installed in raceways for protection from physical damage.
- Proximity to the Transformer: The OCPD protecting the secondary conductors must be installed as close as practicable to where the conductors emerge from the raceway or enclosure.
Why the Secondary Load May Differ from the Transformer’s Full Capacity
For a three-phase transformer, the full-rated capacity is calculated using the following formula:
Secondary Current = Transformer Rating (VA) ÷ (Voltage (L-L) × √3)
For a 75 kVA, 208V three-phase transformer:
Secondary Current = 75,000 ÷ (208 × 1.732) = 75,000 ÷ 360.25 ≈ 208.2 amps
While the transformer can supply up to 208 amps, the connected load often depends on the design of the electrical system and may not use the transformer’s full capacity. In this example, a 100-amp load is used, as the connected equipment and OCPD determine the actual current draw.
Example: Applying the 10-Foot Secondary Conductor Rule
Scenario:
- Transformer Details: A 75 kVA, 480V to 208V three-phase step-down transformer.
- Primary OCPD Rating: 125 amps.
- Secondary Conductors: 2 AWG copper conductors, rated for 115 amps at 75°C.
- Conductor Length: 8 feet (within the 10-foot limit).
- Load: 100 amps (connected equipment).
- Secondary OCPD: 100-amp breaker.
Application:
- Conductor Length: The secondary conductors are 8 feet long, satisfying the 10-foot limit.
- Ampacity Check (General Requirements):
- The secondary conductor ampacity (115 amps) is:
- Greater than the connected load (100 amps).
- Equal to or greater than the OCPD rating at the termination (100 amps).
- Ampacity Check (Field Installation Calculation):
- Primary-to-Secondary Voltage Ratio: 480 ÷ 208 = 2.31.
- Required Ampacity:
- The conductor ampacity (115 amps) exceeds this minimum requirement.
Ampacity = (Primary OCPD Rating ÷ Voltage Ratio) × 0.1
Ampacity = (125 ÷ 2.31) × 0.1 ≈ 5.41 amps
- Overcurrent Protection: A 100-amp breaker is installed at the termination point, providing the required protection.
- Physical Protection: The conductors are installed in a raceway, meeting the NEC requirement for physical protection.
- Proximity to Transformer: The termination point with the OCPD is adjacent to the transformer, meeting the "as close as practicable" requirement.
Conclusion: This installation complies with the 10-foot secondary conductor rule in 240.21(C)(2).
Key Takeaways
- Transformer Capacity vs. Connected Load: While a 75 kVA, 208V three-phase transformer can deliver 208 amps, the connected load and downstream OCPD size (100 amps in this case) determine the actual current demand.
- Accurate Ampacity Calculations: Secondary conductor ampacity must satisfy both the connected load and the formula in 240.21(C)(2) for field installations.
- Conductor Protection: Secondary conductors must be installed in raceways to meet NEC physical protection requirements.
- Proximity to Transformer: OCPDs must be as close as practicable to the point where secondary conductors emerge from the raceway.
Learn More with the Fast Trax® System
The 10-foot secondary conductor rule is just one of many NEC provisions critical for safe, code-compliant electrical installations. To gain mastery of the NEC, explore the Fast Trax® Basic and Enhanced Electrical Exam Prep Courses.
Visit FastTraxSystem.com to elevate your knowledge and advance your career today!
CEO and Founder of Electrical Code Academy, Inc. A Texas Corporation located in McKinney, Texas.
You may also like
Understanding the Rules for Bundling Cables: Applying NEC 310.15(C)(1)(d) for AC and MC Cables
NEC 310.15(C)(1)(d) for AC and MC Cables Understanding the Rules for Bundling Multiconductor Cable Assemblies: Applying NEC 310.15(C)(1)(d) When bundling multiconductor cable assemblies, the National Electrical Code (NEC) provides specific guidance to ensure safety and proper ampacity calculations. One key …
Understanding the Difference Between GFCI and GFP: 2023 NEC
Understanding the Difference Between GFCI and GFP: 2023 NEC The Difference Between GFCI and GFP: Why It Matters in the 2023 NEC Introduction When working with electrical systems, understanding the difference between Ground Fault Circuit Interrupters (GFCIs) and Ground Fault …
GFCI vs. AFCI: Understanding Differences and Dual Function Devices
GFCI vs. AFCI: Understanding Differences and Dual Function Devices Understanding the Differences Between GFCI and AFCI Devices: Dual Function vs. Combination Ratings What is a Ground Fault Circuit Interrupter (GFCI)? A Ground Fault Circuit Interrupter is a device designed to …